HVAC Zone Control Systems
Model ZCV6
6 Zone
HVAC Zone Control Unit
With RS232/RS485
Serial Communications
INSTALLATION AND OPERATION MANUAL
DCN: 141-01068-01
2/06/06
*** IMPORTANT NOTICE ***
DO NOT USE THIS PRODUCT FOR BUILDING FREEZE PROTECTION! YOU ARE ADVISED TO
INSTALL A MECHANICAL FREEZE PROTECTION DEVICE ON YOUR SYSTEM FOR THIS PURPOSE.
RCS
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - Model ZCV6

HVAC Zone Control Systems Model ZCV6 6 Zone HVAC Zone Control Unit With RS232/RS485 Serial Communications INS

Page 2

DCN 141-01068 -01 2/06/06 10 COMMUNICATIONS Communications Setup and Wiring RS232 Communications When the RS232 communications mode is selected,

Page 3 - OPERATION

DCN 141-01068 -01 2/06/06 11 RS485 Communications When the RS485 communications mode is selected, the ZCV6 COM port is a 2 wire (D+ and D –) plus g

Page 4

DCN 141-01068 -01 2/06/06 12 Termination Resistor On multi-drop network wiring, the last device on the network is typically installed with an “end o

Page 5 - STANDARD HVAC SYSTEMS

DCN 141-01068 -01 2/06/06 13 HVAC SYSTEM WIRING Electrically, the ZCV6 Control Unit looks like a standard thermostat to your HVAC system. All conn

Page 6 - HEAT PUMP HVAC SYSTEMS

DCN 141-01068 -01 2/06/06 14 SYSTEM CHECKOUT It is strongly recommended that you hook-up and run a simple bench test before installing this contro

Page 7 - NETWORK OPERATION

DCN 141-01068 -01 2/06/06 15 HVAC SYSTEM QUICK TEST In the event that you have difficulty with the ZCV6 controlling the HVAC system, you can perfor

Page 8 - INSTALLATION

DCN 141-01068 -01 2/06/06 16 ZCV6 6 ZONE HVAC CONTROL UNIT Wiring Diagram Zone Dampers Normally Open RD Series 2 Wir

Page 9

DCN 141-01068 -01 2/06/06 2

Page 10 - COMMUNICATIONS

DCN 141-01068 -01 2/06/06 3 OPERATION The ZCV6 HVAC Zone Control Unit allows a single HVAC mechanical system to be divided into six fully independ

Page 11

DCN 141-01068 -01 2/06/06 4 Outside Temperature Operation The ZCV6 can use and display outside temperature information from a sensor attached to th

Page 12

DCN 141-01068 -01 2/06/06 5 HVAC CONTROL OPERATION AND SETUP STANDARD HVAC SYSTEMS Heat and Cool Mode Operation. In the HEAT mode, the heati

Page 13 - HVAC SYSTEM WIRING

DCN 141-01068 -01 2/06/06 6 HEAT PUMP HVAC SYSTEMS HEAT PUMP SYSTEM OPERATION Heat Pump HVAC Systems use the system’s compressor for both heating

Page 14 - SYSTEM CHECKOUT

DCN 141-01068 -01 2/06/06 7 NETWORK OPERATION The ZCV6 HVAC controller has the option for either RS-232 or RS-485 serial communications. The ser

Page 15

DCN 141-01068 -01 2/06/06 8 INSTALLATION LOCATION AND MOUNTING Install the Control Unit in a protected, convenient, INDOOR location near the HVAC

Page 16 - 6 ZONE HVAC CONTROL UNIT

DCN 141-01068 -01 2/06/06 9 Wiring To The Zone Dampers Wire specification: 2 conductor for RD or 3 conductor for RDM series dampers, standard 18